| Applications |
Fluke 43B |
Fluke 434 |
Fluke 345 |
Fluke 435 |
Fluke VR1710 |
| 1-Phase/3-Phase |
•/- |
•/• |
•/- |
•/• |
•/- |
| Frontline Troubleshooting |
• |
• |
• |
• |
|
| Load study, PQ Survey |
|
• |
|
• |
|
| Compliance (EN50160) |
|
• |
|
• |
|
| Long-term Analysis |
|
|
|
• |
• |
| Features |
Fluke 43B |
Fluke 434 |
Fluke 345 |
Fluke 435 |
Fluke VR1710 |
| Display |
B&W Graphical |
Color Graphical |
Color Graphical |
Color Graphical |
LED |
| Voltage Channels |
1 |
4 |
1 |
4 |
2 |
| Current Channels |
1 |
4 |
1 |
4 |
|
| Included Current Probes |
40A/400A Clamps |
40A/400A Clamps |
2000 A |
3000A Flexis |
|
| Dust/Water Resistance |
IP51 |
IP51 |
IP40 |
IP51 |
IP40 |
| Safety Rating |
600 V CAT III |
600 V CAT IV/1000 V CAT III |
600 V CAT IV |
600 V CAT IV/1000 V CAT III |
300 V CAT II |
| Software |
Fluke View |
Fluke View |
Fluke Power Log |
Fluke Power Log/Fluke View |
Fluke Power Log |
| Battery Operation (hours) |
6.5 |
7 |
24 |
7 |
|
| Recording Capability |
Fluke 43B |
Fluke 434 |
Fluke 345 |
Fluke 435 |
Fluke VR1710 |
| Typical Recording Period (days) |
7 |
7 |
1 |
30 |
30 |
| Memory |
512 KB |
8 MB |
2 MB |
16 MB |
32 KB |
| Min/Max/AVG Logging |
• |
• |
• |
• |
• |
| Flicker |
• |
• |
|
• |
• |
| Harmonics |
• |
• |
• |
• |
• |
| Event Capture |
• |
• |
|
• |
• |
| Waveform Capture |
• |
• |
• |
• |
• |
| User defined Logging |
|
|
|
• |
• |
| Powered off of measured signals |
|
|
|
|
• |
| Sample rate |
12.8 kHz / 15.36 kHz |
20.48 kHz |
9.6 kHz |
20.48 kHz |
1/4 cycle |
| High-speed capture rate |
25 MHz |
200 kHz |
|
200 kHz |
100 µs |
| Peak Voltage |
1.25 kV |
6 kV |
1 kV |
6 kV |
|
| Analysis Capability |
Fluke 43B |
Fluke 434 |
Fluke 345 |
Fluke 435 |
Fluke VR1710 |
| Statistical Analysis (including EN50160) |
|
• |
|
• |
|
| Report Generator |
|
• |
• |
• |
• |
| Accuracy |
Fluke 43B |
Fluke 434 |
Fluke 345 |
Fluke 435 |
Fluke VR1710 |
| IEC 61000-4-30 Class A Compliant |
|
|
|
• |
|
| Volts RMS |
±(1%+10 counts) |
0.5% Vnom |
|
0.1% Vnom |
± 0.5% of range (300 V) |
| Current RMS (excluding clamp unless specified) |
±(1%+10 counts) |
±(1%+5 counts) |
|
±(1%+5 counts) |
|
| ¹ (8 voltage channels without current) |
| ² (except battery housing) |