The Fluke 43 Power Quality Analyzer performs
the measurements you need to maintain power
systems, troubleshoot power problems and
diagnose equipment failures. All in a rugged
handheld package.
Features
New! NiMH Battery provides extended
operating time of 6.5 hours
Combines the most useful capabilities of a
power quality analyzer, multimeter and scope
Calculates 3-phase power on balanced loads,
from a single-phase measurement
Trends voltage, current, frequency, power
harmonics and captures voltage sags,
transients and inrush current
Monitoring functions help track intermittent
problems and power system performance
Records two selectable parameters for up
to 16 days
20 measurement memories to save/recall
screens and data with cursor readings
FlukeView® software can log harmonics
and all other readings over time and provides
a complete harmonics profile up to the
51st harmonic
Measures resistance, diode voltage drop,
continuity, and capacitance
Users/applications manual and power quality
video to help answer tough questions
Complete package with voltage probes and
400 A current clamp, FlukeView Software and
optically isolated interface cable
3 year warranty on the Fluke 43B, 1 year on accessories
Harmonics
Voltage, current, and power harmonics
Up to 51st harmonic
Total harmonic distortion (THD)
Phase angle of individual harmonics
Power
Watts, power factor, displacement power factor (cos Θ), VA and VAR
Voltage and current waveforms
Three phase
On-screen graphics show you how to set up 3-phase power measurements
Sags and swells
Measurements are always automatically recorded to instantly show changes over time
Use cursors to read time and date of sags and swells
Transients
Catch voltage transients and waveform distortion down to 40 nS
Catch and save up to 40 transients
Correlate the cause of transient with time and date stamps
Volts/Ampères/Hertz
Voltage and current waveforms
True RMS voltage and current
Frequency
Specifications
Specifications
Input Characteristics
Input impedance
1 MΩ, 20 pF
Voltage rating
600V rms, CAT III
V/A/Hz Display
True-rms voltage (ac + dc)
Ranges:
5.000 V, 50.00 V, 500.0 V, 1250 V*
Accuracy:
±(1% + 10 counts)
True-rms current (ac + dc)
Ranges:
50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA
Accuracy:
±(1% + 10 counts)
Frequency
Ranges:
10.0 to 15.0 kHz
Accuracy:
± ([% of reading] + [counts]): 0.5% + 2
CF Crest factor
Ranges:
1.0 - 10.0
Accuracy:
±(5% + 1 count)
Power Display
Watts, VA, VAR
1-phase and 3-phase,3 conductor balanced loads
Ranges:
250 W - 1.56 GW
Accuracy:
±(4% + 4 counts) Fundamental Power
Accuracy:
± (2 % + 6 counts) Total Power
PF Power Factor
Range:
0 - 1.0
Accuracy:
±0.04
DPF Displacement Power Factor, Cos .F
Range:
0.25 - 0.9
Accuracy:
±0.04
Range:
0.90 - 1.0
Accuracy:
±0.03
H2 Frequency Fundamental
Ranges:
40.0 to 70.0 Hz
Accuracy:
± ([% of reading] + [counts]): 0.5% + 2
Harmonics Display
Voltage, Current, Frequency
Ranges:
Fundamental to 51st harmonic
Accuracy:
Fundamental:
VA ±(3% + 2 counts) W ±(5% + 2 counts)
2 to 31st harmonic:
VA ±(5% +3 counts) W ±(10% +10 counts)
32 to 51st harmonic:
VA ±(15% +5 counts) W ±(30% +5 counts)
Frequency Fundamental
Ranges:
40 Hz to 70 Hz
Accuracy:
±0.25 Hz
Phase
Range:
V, A (between Fundamental & Harmonics)
Accuracy:
±3º to ±15º
Range:
W (between Voltage Fundamental & Current Harmonics)