The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections. The unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth ground tester, for most electrical grounding work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy grounding tool for electrical contractors, utility test engineers, and earth ground specialists.
Features
3-pole Fall-of-Potential earth testing for basic measurements
2-pole resistance measurements for added versatility
Easily capture values with single-button operation
Ensure accurate measurements with automatic ‘noise’ voltage detection
Hazardous voltage warning offers increased user protection
Clearly read and record data with a large, backlit display
Rugged holster and design for tough work environments
Portable size allows for easy transportation
Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting
600 V Cat II
Specifications
General specifications
Measuring functions
3-pole earth ground resistance, 2-pole ac resistance of a conductor,
Interference voltage
Intrinsic error
Refers to the reference temperature range and is guaranteed for one year
Measuring rate
2 measurements/second
Battery[1]
One 9 volt alkaline (LR61)
Battery condition
LO-BAT is displayed if voltage drops below 6.5 V
Voltages
Between jacks H/C2 and E/C1:
250 Veff maximum (effective voltage)
Between jacks S/P2 and E/C1:
250 Veff maximum
Climatic class
VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87)
Temperature performance[2]
Working:
-10 °C to +50 °C (+14 °F to +122 °F)
Operating:
0 °C to +35 °C (+32 °F to +95 °F)
Storage:
-20 °C to +60 °C (+68 °F to +140 °F)
Reference:
+23 °C ± 2 °C (+73 °F ± 4 °F)
Temperature coefficient
± 0.1 % of range per degree Kelvin
Safety
IEC/EN 61010-1, 600 V CAT II, pollution degree 2
Dimensions
113 mm x 54 mm x 216 mm (4.5 in x 2.1 in x 8.5 in), including holster
Weight
850 g (1.9 lb), including standard accessories, volume approximately 600 cm3
Note:
[1]If the tester is not going to be used, or is being stored for a long period, remove the battery and store separately from the tester to avoid
damage from battery leakage.
Note:
[2]The four temperature ranges for the tester exists to satisfy European Standards requirements; the instrument can be used over the full
working temperature range by using the temperature coefficient to calculate accuracy at the ambient temperature of use.
Electrical specifications
Maximum deviations:
E1 Influence factor
Position
E1 Deviation influence
0 %
E2 Influence factor
Supply voltage
E2 Deviation influence
0 %
E3 Influence factor
Temperature E3
E3 Deviation influence
2.3 %
E4 Influence factor
Serial interference voltage (20 V)
E4 Deviation influence
0.6 %
E5 Influence factor
Probe- and auxiliary probe resistance
E5 Deviation influence
10 %
Test voltage
3.7 kV
Protection type
IP 40; IEC/EN 60529
Electromagnetic compatibility
Emission: IEC/EN 61326 Class B
Immunity: IEC/EN 61326 Annex C
RE resistance measurement
Measuring method
Current-voltage measurement with improved cross-talk attenuation,
no compensation of measuring lead resistance, with probe (3-pole)
or without probe (2-pole), as per IEC/EN 61557-5
Open circuit voltage
23 to 24 V ac
Short circuit current
> 50 mA ac
Measuring frequency
128 Hz
Maximum permissible
overload
250 Veff
Measuring time
8 seconds (average from when START is pressed)
Limit input
Tester retains set value even if instrument is turned off (assuming
battery power supply is sufficient)
Automatic changeover of resolution
RH
< 7 kΩ
Resolution
0.01 Ω
RH
< 50 kΩ
Resolution
0.1 Ω
RH
> 50 kΩ
Resolution
1 Ω
Interference voltage display dc + ac
Vmax
30 Veff
Common mode rejection
> 80 dB at 50 Hz and
60 Hz
Ri
680 kΩ
Measuring uncertainty
< 10 % for pure ac
and dc signals
Measuring
range
0.15 Ω to 20 Ω
Resolution
0.01 Ω
Display range
0 to 19.99 Ω
200 Ω
Resolution
0.1 Ω
Display range
20 to 199.9 Ω
2 kΩ
Resolution
1 Ω
Display range
200 to 1999 Ω
Intrinsic uncertainty
± (6 % of
measured value
+ 5D)
Operating uncertainty IEC 61557[1]
± (18 % of measured value + 5D)
Notes:
[1] Covers all deviations caused by influence quantities E1-E5.
If the deviation E4 caused by high probe or auxiliary probe resistance is higher than specified flashes.
Measured values are outside of the specified operating uncertainty.
Models and Accessories
Model name
Description
Buy it **
Fluke 1621
Earth Ground Tester
1621 includes:
Users manual
Two measuring leads with alligator clips, 2 m (6 ft)