Pinpoint power quality problems faster, safer and in greater detail
These three-phase power quality meters help you locate, predict, prevent and troubleshoot problems in power distribution systems. These easy-to-use power quality tools are a “must have” for any person who maintains or troubleshoots three phase power. The new IEC Class A standards for flicker and power quality are built right in to take the guess work out of power monitoring.
Applications
- Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
- Predictive maintenance – detect and prevent power quality issues before they cause downtime
- Quality of service compliance – validate incoming power quality at the service entrance
- Long-term analysis – uncover hard-to-find or intermittent issues
- Load studies – verify electrical system capacity before adding loads
- Energy assessments – quantify energy consumption before and after improvements to justify energy saving devices
|
|
- Troubleshoot real-time: Analyze the trends using the cursors and zoom tools—even while background recording continues
- Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance
- Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV
- Fully Class A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class A standard
- Measure all three phases and neutral: With included four current probes
- AutoTrend: Every measurement you see is always automatically recorded, without any setup
- System-monitor: Up to seven power quality parameters on one screen according to EN50160 power quality standard
- Inrush mode: For troubleshooting nuisance circuit breaker tripping
- View graphs and generate reports: With included analysis software
- Logger function: Configure for any test condition with memory for over 400 parameters at user defined intervals
- Mains signaling: Measure interference from ripple control signals at specific frequencies
- Battery Life: Seven hours operating time per charge on NiMH battery pack
- Warranty: Rugged, handheld troubleshooter with Fluke three-year warranty
|
|
| Technical Data |
| Inputs |
| Number: |
4 voltage and current (3 phases + neutral) |
| Maximum voltage: |
1000 Vrms (6 kV peak) |
| Maximum sampling speed: |
200 kS/s on each channel simultaneously |
| | Volt/Amps/Hertz |
| Vrms (AC + DC) |
|
| Measurement range: |
1 ... 1000 V |
| Accuracy: |
0.1% of Vnom |
|
|
| Vpeak |
|
| Measurement range: |
1 ... 1400 V |
| Accuracy: |
5% of Vnom |
|
|
| Crest factor, voltage |
|
| Measurement range: |
1.0 ... > 2.8 |
| Accuracy: |
±5% |
|
|
| Arms (AC + DC) |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±0.5% ± 5 counts |
|
|
| Apeak |
|
| Measurement range: |
0 ... 5.5 kA |
| Accuracy: |
5% |
|
|
| Crest factor, A |
|
| Measurement range: |
1 ... 10 |
| Accuracy: |
±5% |
|
|
| Hz 50 Hz nominal |
|
| Measurement range: |
40 ... 70 Hz |
| Accuracy: |
±0.01 Hz |
| | Dips and swells |
| Vrms (AC+DC) ² |
|
| Measurement range: |
0.0% … 100% of Vnom |
| Accuracy: |
±0.2% of nominal voltage |
|
|
| Arms (AC+DC) ² |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
| | Harmonics |
| Harmonic (interharmonic) (n) |
|
| Measurement range: |
DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7 |
|
|
| Vrms |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±0.05% of nominal voltage |
|
|
| Arms |
|
| Measurement range: |
0.0 … 4000 mV x clamp scaling |
| Accuracy: |
±5% ± 5 counts |
|
|
| Watts |
|
| Measurement range: |
Depends on clamp scaling and voltage |
| Accuracy: |
±5% ± n x 2% or reading, ± 10 counts |
|
|
| DC voltage |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±0.2% of nominal voltage |
|
|
| THD |
|
| Measurement range: |
0.0 … 100.0% |
| Accuracy: |
±2.5% V and A (± 5% Watt) |
|
|
| Hz |
|
| Measurement range: |
0 … 3500 Hz |
| Accuracy: |
± 1 Hz |
|
|
| Phase angle |
|
| Measurement range: |
-360º ... +360º |
| Accuracy: |
± n × 1.5º |
| | Power and energy |
| Watt, VA, VAR |
|
| Measurement range: |
1.0 … 20.00 MVA¹ |
| Accuracy: |
±1% ± counts |
|
|
| kWh, kVAh, kVARh |
|
| Measurement range: |
00.00 …200.0 GVAh¹ |
| Accuracy: |
± 1.5% ± 10 counts |
|
|
| Power Factor/ Cos Ф / DPF |
|
| Measurement range: |
0…1 |
| Accuracy: |
± 0.03 |
| | Flicker |
| Pst (1 min), Pst, Plt, PF5 |
|
| Measurement range: |
0.00 … 20.00 |
| Accuracy: |
±5% |
| | Unbalance |
| Volts |
|
| Measurement range: |
0.0 … 5.0% |
| Accuracy: |
±0.5% |
|
|
| Current |
|
| Measurement range: |
0.0 … 20% |
| Accuracy: |
± 1% |
| | Transient Capture |
| Volts |
|
| Measurement range: |
±6000 V |
| Accuracy: |
±2.5% of Vrms |
| Minimum detect duration |
5 µs (200kS/s sampling) |
| | Inrush mode |
| Arms (AC+DC) |
|
| Measurement range: |
0.000 … 20.00 kA¹ |
| Accuracy: |
±1% of meas ± 5 counts |
|
|
| Inrush duration (selectable) |
|
| Measurement range: |
7.5 s ... 30 min |
| Accuracy: |
±20 ms (Fnom = 50 Hz) |
| | Autotrend recording |
| Sampling: |
5 readings/sec continuous sampling per channel |
| Memory: |
1800 min, max and avg points for each reading |
| Recording time: |
Up to 450 days |
| Zoom: |
Up to 12x horizontal zoom |
| | Memory |
| Screens & data: |
50, shared memory divided between logging, screens and data sets |
| | Notes |
| ¹ |
Depending on clamp scaling |
| ² |
Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle
|
|
The advanced functions Interharmonics, Energy, Transients and Inrush are optional for the Fluke 434 and standard
available on the Fluke 435.
| Environmental Specifications |
| Operating Temperature | |
| Safety Specifications |
| Safety |
|
EN61010-1 (2nd edition) pollution degree 2; 1000 V CAT III / 600 V CAT IV
ANSI/ISA S82.01
|
|
| Mechanical & General Specifications |
| Size | | | Weight | | | Battery Life |
| Rechargeable NiMH pack (installed): |
>7 hours |
| Battery charging time: |
4 hours typical |
| | Shock & Vibration |
| Shock: |
30 g |
| Vibration: |
3 g according to MIL-PRF-28800F Class 2 |
| | Case |
|
Rugged, shock proof with integrated protective holster, IP51 (drip and dust proof) |
| | Warranty | |
|
| Model name | Description | Buy it ** | | Fluke 434 | Power Quality Analyzer
Includes:
- Hard carrying case
- 4 current probes (i400s)
- 5 test leads and clips
- Battery charger
- FlukeView® software
- Optical USB cable
- Color localization set
- Getting Started manual
- Users manual on CD-ROM
|
|  | | | Fluke 435 | Includes:
- Hard carrying case with rollers
- Four flexible current probes (i430-flex)
- 5 test leads and clips
- Battery charger
- FlukeView® software
- PowerLog® software
- Optical USB cable
- Color localization set
- Getting Started (printed)
- User Manual (CD-ROM)
|
|  | |
The Basic models do not include current measuring probes, these must be ordered seperately
IEC 61000-4-30 Class-A Compliance
|
435
|
434
|
| Measurement algorithms |
• |
• |
| Voltage accuracy |
0.1% of Vnom |
0.5% of Vnom |
| Time synchronization |
optional with GPS430 accessory |
Power Quality Analyzer Selection Table
|
435
|
434
|
| Measures voltage, current, dips, swells, interruptions, harmonics, inter-harmonics, flicker, power, energy, transients, frequency, unbalance, inrush, EN5160 overview |
• |
• |
| Logger function with multi-parameter logging |
• |
optional* |
| Mains signaling |
• |
optional* |
| Memory size |
16 MB |
8 MB |
| Current probes |
3000 A flexible (4) |
40 A/400 A clamp (4) |
| Carrying case |
water-tight hard case with rollers |
rugged hard case |
| Software |
Fluke Power Log and FlukeView® |
FlukeView® |
*Optional functionality can be added with upgrade kit
|
| Test Leads Probes and Clips | Buy it ** | | AC285 | SureGrip™ Alligator Clips |  |  | | TLS430 | Test Leads and Alligator Clips (4 black, 1 green) |  |  |
| Cases-Holsters | Buy it ** | | C435 | Hard Rolling Case | | | | Fluke MeterCleaner Wipes | Fluke MeterCleaner Wipes | |  |
| Current-Clamps | Buy it ** | | 5 A ac Current Clamps |  |  | | Flex 4 Pack |  |  | | AC Current Clamp |  |  | | Flex Current Clamp |  |  | | i1000s | AC Current Clamp (1000 A) |  |  | | i200s | AC Current Clamp |  |  | | i3000s | AC Current Clamp (3000 A) |  |  |
| Batteries, Chargers and Adapters | Buy it ** | | BC430 | Line Voltage Adapter/Battery Charger | |  | | BP190 | Rechargeable NiMH Battery Pack | |  |
| Cables and Hardware | Buy it ** | | OC4USB | USB interface cable | |  | | PAC91 | Printer Adapter Cable | |  | | PM9080 | Optically Isolated RS-232 Adapter | |  |
|
|
|
|
 |
 | | Search Fluke | | | | | | | | | | | | | | | | | | | | | | | | Find Resources | | | | | | | | |
|
|
 |
|
|
|
|
|
|
|
 |
| |